NETMAND AND MULTICOM INTERFACES AND ADAPTERS

For Riello Galatrek UPS systems 350VA-6MVA A wide range of interface kits, cables, SNMP adapters, USB converters
and MultiPlexers is available to help you get the most from your
UPS. Specialist advice can be obtained from our sales and technical
teams.
NETMAN 101/102
The NetMan network agent allows UPS management across a LAN using
any of the main network communication protocols - TCP/IP, HTTP
and network interface (SNMP). NetMan enabled UPS integrate
easily into medium and large sized networks and provide reliable
communications between the UPS and management systems employed.
• Configured via TELNET or a serial terminal
•
Compatible with PowerShield² and PowerNETGuard control software
• Integrated Web server for browser-based display
• TeleGuard modem compatible
• Firmware upgradeable through the serial port.
• Supports the network interface (SNMP) standard communication
protocol with proprietary RFC 1628 and MIB
MULTICOM 301/302
The MultiCOM 301/302 protocol converter may be used to monitor
the UPS using the MODBUS/JBUS protocol on RS485 or RS232 serial
lines. It will also manage a second, independent RS232 serial
line that can be used to connect other devices such as the
Netman 101 or a PC that uses the PowerShield² software.
• Configuration of the port for MODBUS/JBUS as RS232 or RS485
• Management of two independent serial lines
• Suitable for integration with Building Management Systems (BMS)
• LED signalling of the communication flow
• Firmware upgradeable through the serial port.
MULTICOM 351/352
The MultiCom 351/352 is a serial duplexer that allows two devices
to be connected to a single serial port on a UPS. It can be used
where numerous serial connections and multiple polling of UPS
are required, and is ideal for LAN networks with a firewall.
• Cascading configuration giving a maximum of 4 serial ports
• LED signalling of the communication flow
• Firmware upgradeable through the serial port.
MULTI I/O
The Multi I/O device integrates the UPS with control systems
with complete configurability of the input and output signals.
• 8 analog/digital inputs
• 8 relay outputs configured using the UPS and input status
• May communicate with the UPS via RS-232
• can control 2 independent serial lines RS232/RS485 to monitor
the UPS and the device itself with the Modbus/Jbus protocol.
USB Converter
The RS232-USB converter allows UPS without a USB port to connect
to Macintosh, Windows and linux PCs with this type of port.
• compatible with USB 1.2
• compatible with PowerShield²
POWERSHIELD² UPS Monitoring and Control
Software
350VA-6MVA

For Riello Galatrek UPS systems on Windows, Novell, Unix and
MAC operating systems
POWERSHIELD² provides user-friendly UPS
management. The software displays real time information in
the form of bar charts
and values for critical data such as mains voltage, UPS load
and battery charge%. The software allows remote interrogation
of UPS logs and operating parameters to help diagnose alarms
and potential fault conditions.
OPERATING SYSTEMS SUPPORTED
• Windows 95-OSR2, 98, Me, NT 4.0, 2000, XP, 2003
• Linux
• Novell Netware 3.x, 4.x, 5.x, 6
• Mac OS X, 9.x
• IBM OS/2 Warp and Server
• HP OPEN VMS
• The most widely used UNIX operating systems such as: IBM AIX,
HP UNIX, SUN Solaris INTEL and SPARC, SCO Unix and UnixWare,
Silicon Graphic IRIX, Compaq Tru64 UNIX and DEC UNIX, BSD UNIX
and FreeBSD UNIX, NCR UNIX.
CHARACTERISTICS
•
Sequential and priority-based shutdown: PowerShield² provides
unattended shut-down of single and networked PCs, saving any
active work and the most widely used applications Windows. Users
can define their own shutdown procedures and establish the order
in which critical computers (such as servers) are to be powered
down.
• Multi-platform compatibility: PowerShield² uses
the TCP/IP comunications protocol to achieve standardised management
and monitoring across the widest possible range of platforms.
This makes it possible to monitor computers with different operating
systems from a single console, for example monitoring a UNIX
server from a PC with Windows and also connecting to UPS located
in different geographical areas using dedicated networks (intranets)
or the Internet.
• Event scheduling: PowerShield² users
can program their own shutdown procedures, detailing power-off
and power-up
scenarios to increase system safety and, equally important, power
economy.
• Messages management: PowerShield² keeps
users constantly informed about the status of their local and
network UPS. A list
can be defined of users who should receive e-mail messages, faxes
and SMS when faults or sudden blackouts occur.
• Integrated SNMP agent: PowerShield² features
an integrated SNMP agent for management of the UPS. This agent
is
able to send all the UPS information and generate traps using
the RFC 1628 MIB standard. This makes it possible to manage the
UPS in compatible SNMP management stations such as HP Open View,
Novell Managewise and IBM NetView.
• Wap server integrated: PowerShield² allows
the user to monitor the UPS through WAP mobile phone.
• Security, easy to use and connect: communication
is password protected to ensure UPS system security. Using
the new
discovery/browsing function, all the RIELLO UPS connected to
a protected computer or LAN can be displayed in a list format.
In the absence of a LAN connection, support is provided for modem-based
communication
Click
here for Powershield Brochure (PDF 1,229KB) |